Cable sheat fault detection procedure
Technical articles
MRT-700 is able to detect ground faults on pipes and cables (for this purpose the device must be requested with location functionality). These faults are caused by the deterioration of the coating on pipes and damages in the isolation of the cables, therefore the metallic part of them may make contact with the ground.
In order to perform fault location works it is necessary to use a special frequency – 8KFF – in both transmitter and receiver, and an external sensor – A-Frame – connected to the receiver in order to measure this frequency.
It’s recommended that the conductor to be identified to be completely open at both ends, for this purpose, any connection to ground must be eliminated. If any connection was maintained, this would be the path chosen by the signal to escape to ground and the fault location operation will be much more difficult.
Transmitter connection
Fault locating can only be achieved with direct connection, so connect crocodile clamps to “Active signal out” connector of the transmitter. Then connect red cable to the conductor of the cable to be located and black cable to the earth spike. It is important to avoid connecting the transmitter when it is turned on or transmitting because high voltages can be generated between clamps.
The spike must be correctly connected to earth in order to achieve a good return of the signal. It is recommended that earth spike to be the first element to be connected and the last one to be disconnected. Place the transmitter and the earth spike as far away as possible from the conductor and the cables, in a 90º angle with the direction of the cable with the connection is being made. This positioning prevents the return of the signal from distorting the location results.
Once the transmitter installation has been completed, assuring a good returning path through the earth, turn on the transmitter and select the -8KFF- frequency and the signal injection level.
Receiver settings
After the A-Frame is connected to the receiver, it will be detected automatically and 8KFF will appear on the display, indicating that the receiver is already in fault locating mode. There are two display modes: a basic one which only shows information regarding to fault locating and advanced one which displays the information corresponding to the fault locating feature combined simultaneously with the “standard” tracing display.
Display Mode Advanced
Before starting
It is recommended getting a reference measurement in the area close to the transmitter. It will give us a first approximation about the severity of the fault and also if there is one or more faults along the conductor. In case that there was only one fault in the conductor, the measurement shown in the screen should be similar as the reference measurement. However, if there are more faults, measurement value will be distributed among them depending on their severity.
Fault locating procedure
Starting from the transmitter (with red mark of the A-Frame pointing to the fault, the opposite way from the transmitter location) the path of the conductor must be followed placing the spikes of the A-Frame in contact with the surface. The process of tracing the conductor is much easier with the display in advanced mode that lets the user analyze the fault measurements while tracing the conductor.
As the user moves away from the transmitter the dBs measurement will decrease and the direction of the arrow could fluctuate or disappear completely. The distance between the spike and this “minimum measurement” can be taken as safety reference distance, that means this is the distance that must be taken between two consecutive measurements with the A-Frame.
When getting close to a fault, the arrow will point in the direction of the fault and measurements in dBs shown in the screen will increase. In the faulty area, it is recommended to reduce the distance between measurements. The highest magnitude measurements in dBs will be taken before and after the fault, while the value will be reduced to its minimum above the fault. In addition, as soon as the fault is exceeded, the direction arrow will change its direction indicating the fault is behind us.
Even though that the cable path it´s known, it´s recommended to perform a side sweep with the A-Frame to assure the positioning of the fault. For that, in the determined point the A-Frame must be turned 90º and carry out the same process. The magnitude measurements will behave in the same way; so that the point in which the direction of the arrow changes will be the point where the fault is located.
If the dBs measurements in the faulty area are similar to the reference measurement it indicates that this is the unique fault in the conductor, if not, the conductor inspection works should be resumed in order to other possible faults. It could also happen that there are faults with big difference of severity (impedance). A high severity fault could complicate the detection of other low severity faults, in these cases it is recommended to solve the fault and the repeat the identification process.
When the conductor is under a paved surface, sometimes the fault can be located by working in the land adjacent to it. In case that there is not possible of doing that, many times signals can be detected directly on the pavement. To improve the grounding of the A-Frame spikes, a small amount of water can be poured over them.
Do you want to know more about this topic or our devices? Click on the link!
La entrada Cable sheat fault detection procedure se publicó primero en Merytronic.
Related News
Sustainability report 2023
In this report, you will obtain information on what has been done in the areas...
Gorlan, honorable mention in the category ‘Walking towards Well-being”
We have been awarded in the 10th edition of the Scholastic Zaldívar Fraternity-Muprespa Awards for...
Sustainability report 2022
In this report, you will obtain information on what has been done in the areas...